UMG 96RM-M

UMG 96RM-M UMG 96RM-M UMG 96RM-M

We will be happy to advise you:

UMG 96RM-M

UMG 96RM-M - 5222069 Three-phase network analyzer with rated voltage up to 277/480 V AC. Supply voltage 90-277 V AC, 90-250 V DC. M-Bus interface, GridVis software.
339 € excl. VAT
410,19 € incl. VAT

Recycling fee 1 € included in the price

In stock
Order number: 5222069
EAN: 4251861100040

The UMG 96RM is a measurement instrument of the newest generation which is suitable for measuring, recording and monitoring electrical parameters (True-RMS) in low and medium voltage networks (1 and 3-phase systems with a neutral conductor).

In order to record work values securely and precisely for individual consumers, the UMG measuring devices have an extensive selection of tariffs of up to 14 items depending on the device type. Of course, they differentiate between effective energy (consumption, supply and without backstop) and reactive energy (inductive, capacitive and without backstop). This can be used to record high and low tariffs separately for example.

Harmonics occur due to operating equipment with a non-linear characteristic, e.g. transformers used in saturation, energy saving bulbs, frequency converters and power electronics. They cause a load on the mains due to additional currents and can affect or even destroy operating equipment. This mains feedback can be detected and documented using power quality analysers.

Pulse inputs can be used to record the values for meters such as water and gas meters using UMG measuring devices. Using pulse outputs as a measured value transducer, the working pulses can be transferred to a control system such as BCS, PLC, SCADA systems.

The high accuracy of measurement is due to the high sampling rate and very good long-term stability. If used as intended (ambient temperature!), accuracy of measurement is always better even after years of use than that of conventional meters immediately after delivery. Devices that are certified according to class A are available for measuring tasks that are particularly demanding.

Areas of application

  • Measurement, monitoring and checking of electrical characteristics in energy distribution systems
  • Recording of load profiles for energy management systems (e.g. ISO 50001)
  • Acquisition of the energy consumption for cost centre analysis
  • Measured value transducer for building management systems or PLC (Modbus)
  • Compact construction saves space and costs during installation
  • Seamless and sustained recording thanks to large measured data memory or via the online data acquisition (e.g. GridVis®-Service)
  • High data security and redundancy
  • Comprehensive communications options and protocols
  • Multifaceted, pre-defined reports for power quality and energy consumption analysis (via GridVis®-Service)
  • Simple report generation at the press of a button or automatically in accordance with defined time plans
  • Precision measurement results provide an effective infrastructure as well as high production availability
  • Generic Modbus profile: Arbitrary Modbus-capable devices and systems from other manufacturers can be incorporated and visualised in the monitoring solutions
  • Long-term availability of the measurement devices guarantees simple retrofitting with system expansions
  • Detailed acquisition of the energy data and the load profile
  • More transparency in energy supply through energy analyses
  • Safer design of the power distribution systems
  • Determination of energy costs
  • Breakdown and allocation of energy consumers
  • Continuous increase in energy efficiency
  • Cost reduction
  • UMG 96RM series multifunctional power analysers are an important part of energy management systems
  • More transparency through a multi-stage, scalable measurement system
  • Acquisition of individual events through continuous measurement with high resolution
  • Notification of inadequate power quality
  • Introduction of measures to address network problems
  • Prevention of production downtimes
  • Significantly longer service life for equipment
  • Improved sustainabilityt
  • High sampling rate at 21.3 kHz
  • Reliable measurement accuracy of 0.2 % (V)
  • Effective energy class (kWh): 0.5
  • Energy measurement in 4 quadrants, each with 7 tariffs for effective and reactive energy
  • Safe and precise acquisition of operational values for individual electrical loads
  • Numerous interfaces and protocols, guaranteeing an easy system connection (energy management system, PLC, SCADA, BMS
  • Harmonics analysis up to 40th harmonic
  • Information about power quality, grid disturbances and possible "network polluters"
  • Convenient installation even where spaces are tight
  • Large, high-contrast LCD display with backlighting
  • Very good readability and intuitive operation, even in poor lighting conditions
  • The Profibus connection is used in systems where the UMG 96RM-P is to be incorporated into the automation environment (PLC controllers)
  • The UMG 96RM-M can be simply and cost-effectively integrated into consumption data acquisition systems via the M-Bus connection
  • The M-Bus is primarily used for the acquisition of consumption data collection from various different consumption meters, such as water, gas, heat or electrical current
Rated voltage [V] L-N: 277 V AC, L-L: 480 V AC
Power voltage [V] 90 - 277 V AC, 90 - 250 V DC
Accuracy class 0,5S (kWh,.../5 A)
Width [mm] 96
Height [mm] 96
Depth [mm] 48
Weight in [g] 300
Software GridVis - Basic
Communication interface M-Bus
Protocols BEZ
Overvoltage category 300 V CAT III
Distortion factor THD-U, THD-I YES
Connection (L-N, L-L) 3 / 4 - conductive
Measurement type 4-quadrant
Current measurement channels NO
Digital inputs 2
Digital / pulse output 3
Sampling frequency 50/60 Hz 21,33 / 25,6 kHz
Number of measurement records per second 21.330 / 25.600
Number of measuring results per second 5
Transients NO
Flicker measurement NO
Clock NO
Accuracy V/A 0,2 % / 0,2 %
Integrated logic NE
Number of stored values ​​in memory NE
Weekly timer NE
Uninterruptible measurement YES
Short-term event outages (recording) NE
Measuring asymmetry NO
Residual current measurement NO
Recording of error events NE
Consecutive / backward / null component ANO
Bi-metallic function ANO
Operating hours counter ANO
Input for temperature measurement Komparátory
RMS value of periods (50/60 Hz) 10/12

Accessories