UMG 96-PQ-L-LP, 90-277V
We will be happy to advise you:
UMG 96-PQ-L-LP, 90-277V
From power quality analysis to energy monitoring, from residual current to temperature monitoring, the UMG 96-PQ-L-LP offers the right functions for every application. Avoid system failures by clearly displaying the entire power quality of a measurement level at low cost with the UMG 96-PQ-L-LP.
Short of space in the switchboard cabinet? Thanks to the low-power current inputs, classic current transformers can be replaced with smaller and less expensive current transformers. Since low-power transformers operate in the millivolt range on the secondary side, no converter disconnect terminal is required.
Passive Rogowski coils can also be used for simple retrofit solutions. In this case, the measurement device serves as the measurement transducer, saving money and essential space in the switchboard cabinet.
The UMG 96-PQ-L-LP modular network analyzer can measure full-wave events and present and analyze them directly in the network display. It also comes with a large memory, which, thanks to a special data compression method, ensures several years’ worth of storage. Memory partitioning preserves the long storage time for current, power and work even in combination with high-resolution power quality measurement.
All values can be conveniently displayed and graphically represented on the color graphic display. What’s more, the UMG 96-PQ-L-LP offers plug-in modules for functional enhancements and 50 comparators that can be configured individually or via predefined comparator profiles.
Low-power inputs
- Switchable current measuring channel
- Low-power current measuring channel for low-cost 333 mV current transformer
- Current measurement with passive Rogowski coils e.g. 100 mV/1 kA
Power quality
- Harmonics current up to the 65th harmonic
- High sampling rate with 280 sampling points per full wave
- 20 ms RMS value memory for full-wave events
Energy management
- Identify savings potentials
- Active energy class 0.5 S
- Compliance with regulatory and tax requirements Configurable screened average values
Visualization
- Oscilloscope function
- Phasor diagram on the display
- History of drag indicator values on the display
- Resetting of the drag indicator values via display or remotely
Operation
- 6-button operation on the color graphic display
- Intuitive operation
- Configuration directly on the display
- On-site operation
- Configurable home screen and jump-back point
Events
- Representation in the display
- Read out last event via Modbus
- Display root-mean-square value curves in the GridVis® event browser
Modularity
- Temperature measurement with monitoring via integrated comparator
- Ethernet interface and Modbus gateway
- Multifunction inputs for residual current measurement or DC power measurement
Limit value monitoring
- 50 comparators in the device
- Hysteresis
- Predefined comparator profiles for quick configuration (GridVis®)
Peripherals
- 3 digital outputs
- 1 analog output
- 3 digital inputs
- 4 power inputs directly from the basic device
Installation & integration
- Overvoltage category 600 V CAT III / 300 V CAT IV
- Easy installation thanks to 96 x 96 mm front panel
- Time setting via third-party systems according to EN 60870-5-4:1993
- Serial interface with Modbus RTU
Communication
- Client / Server*
- Gateway function*
- Ethernet interface*
- RS-485
- 5 simultaneous Modbus TCP connections*
*with module 96-PA-RCM-EL
Memory
- High memory depth with low memory requirements
- Memory depth up to 15 years with 23 measured values of 15 min each and 8 measured values of 1 h each
- Memory partitioning into long-term memory and high-resolution PQ short-term memory
| Rated voltage [V] | L-N: 600 v AC,L-L: v AC 720 v AC |
|---|---|
| Power voltage [V] | 24 - 90 V AC, 24 - 90 V DC |
| Width [mm] | 96 |
| Height [mm] | 96 |
| Depth [mm] | 86 |
| Weight in [g] | 250 |
| Software | GridVis - Basic |
| Communication interface | RS-485 |
| Protocols | Modbus RTU |
| Memory | 64 MB Flash |
| Overvoltage category | CAT II 300V, CAT III 600V |
| Distortion factor THD-U, THD-I | YES |
| Connection (L-N, L-L) | 3 / 4 - conductive |
| Measurement type | 4-quadrant |
| Current measurement channels | 1 |
| Digital inputs | 3 |
| Digital / pulse output | 3 |
| Sampling frequency 50/60 Hz | 13,67 kHz |
| Number of measurement records per second | 13.670 |
| Number of measuring results per second | 3 |
| Transients | NO |
| Flicker measurement | YES |
| Clock | YES |
| Accuracy V/A | 0,2 % / 0,2 % |
| Integrated logic | Jasic (7 Prg.) |
| Weekly timer | NE |
| Uninterruptible measurement | YES |
| Short-term event outages (recording) | ANO |
| Measuring asymmetry | NO |
| Residual current measurement | YES |
| Recording of error events | ANO |
| Consecutive / backward / null component | NE |
| Bi-metallic function | ANO |
| Operating hours counter | ANO |
| Input for temperature measurement | Komparátory |
| RMS value of periods (50/60 Hz) | 10/12 |
Návody
The highlighted items are mandatory.