UMG 96-PQ-L, 90-277V

UMG 96-PQ-L, 90-277V UMG 96-PQ-L, 90-277V

We will be happy to advise you:

UMG 96-PQ-L, 90-277V

UMG 96 PQ-L, 90-277V - 5236001 Three-phase network analyzer with rated voltage up to 347/600V AV. Supply voltage 24-90 v AC, 24-90 v DC. Flash memory 64 MB, RS 485 interface, GridVis software, LCD display
521 € excl. VAT
630,41 € incl. VAT

Recycling fee 0,50 € included in the price

In stock
Order number: 5236001
EAN: 4251861102570

Whether power quality analysis, residual current monitoring or temperature monitoring, the UMG 96-PQ-L offers the right functions for every application. With the UMG 96-PQ-L, it is now possible to cost-effectively ensure complete power quality transparency at every level and thus avoid system failures.

Full-wave event measurements can be shown and analysed directly on the display. In addition, the modular network offers a large memory, which thanks to a special data compression method, ensures several years’ worth of storage.

Memory partitioning preserves the long term storage for current and power data and allows the combination of storing high-resolution power quality measurements. This storage partitioning helps extend the amount of data that is being stored at a higher performance while keeping costs of hardware low.

All values can be conveniently displayed and graphically represented on the color graphic display.

Power quality

  • Harmonics current up to the 65th harmonic
  • High sampling rate with 280 sampling points per full wave
  • 1 ms digital input event capture rate
  • 20 ms RMS value memory
  • Full-wave events

Visualization

  • Oscilloscope function
  • Phasor diagram on the display
  • Drag indicator history on the display
  • Resetting of the drag indicators via display or remotely

Installation & Integration

  • Overvoltage category 600 V CAT III
  • Easy installation thanks to 96 x 96 mm front panel
  • Use in IT networks with variants 52.36.005
  • Time setting via third-party systems according to DIN 60970-5-4

Energy management

  • Identify savings potentials
  • Active energy class 0.2S#
  • Compliance with regulatory and tax requirements
  • Configurable screened average value

Memory

  • High memory depth with low memory requirements
  • Storage depth up to 15 years with 23 measured values of 15 min. each and 8 measured values of 1 h each
  • Memory partitioning into long-term memory and high-resolution PQ shortterm memory

Modularity

  • Temperature measurement with monitoring via integrated comparator
  • Ethernet interface and Modbus gateway
  • Multifunction inputs for residual current measurement or DC power measurement
  • Neutral conductor measurement (I4 – current measurement)

Peripherals

  • 3 digital outputs
  • 1 analog output
  • 3 digital inputs

Communication

  • Modbus Client/Server gateway functionality
  • Gateway function
  • Ethernet interface
  • RS485
  • 5 simultaneous Modbus TCP connections

Operation

  • 6-button operation on the color graphic display
  • Intuitive operation
  • Configuration directly on the display
  • On-site and remote operation with GridVis®
  • Configurable home screen and jump-back point

Comparator

  • 50 comparators in the device
  • Hysteresis
  • Predefined comparator profiles for quick configuration (GridVis®)

Class S

  • Flicker
  • Interharmonics
  • Standard-compliant PQ data based on, e.g. EN 50160 and IEEE519
  • Rapid voltage change
  • Overfrequencies & underfrequencies
  • Predefined recording profiles for EN 50160, IEEE519,61000-2-4, AHF and SVG

Rated voltage [V] L-N: 600 v AC,L-L: v AC 720 v AC
Power voltage [V] 90 - 277 V AC, 90 - 250 V DC
Accuracy class 0,2S (kWh,.../5 A)
Width [mm] 96
Height [mm] 96
Depth [mm] 86
Weight in [g] 250
Software GridVis - Basic
Communication interface RS-485
Protocols Modbus RTU
Memory 64 MB Flash
Overvoltage category CAT II 300V, CAT III 600V
Distortion factor THD-U, THD-I YES
Connection (L-N, L-L) 3 / 4 - conductive
Measurement type 4-quadrant
Current measurement channels 1
Digital inputs 3
Digital / pulse output 3
Sampling frequency 50/60 Hz 13,67 kHz
Number of measurement records per second 13.670
Number of measuring results per second 3
Transients NO
Flicker measurement YES
Clock YES
Accuracy V/A 0,2 % / 0,2 %
Integrated logic Jasic (7 Prg.)
Weekly timer NE
Uninterruptible measurement YES
Short-term event outages (recording) ANO
Measuring asymmetry NO
Residual current measurement YES
Recording of error events ANO
Consecutive / backward / null component NE
Bi-metallic function ANO
Operating hours counter ANO
Input for temperature measurement Komparátory
RMS value of periods (50/60 Hz) 10/12

Accessories

No item