UMG 605-PRO

UMG 605-PRO UMG 605-PRO UMG 605-PRO

We will be happy to advise you:

UMG 605-PRO

UMG 605 - 5216028 Three-phase network analyzer with rated voltage up to 277/480 V AC. Supply voltage 50-110 V AC, 50-155 V DC. Flash memory, capacity 128 MB. Interfaces RS 232, RS 485, Profibus DP, Ethernet, GridVis software.
1 242 € excl. VAT
1 502,82 € incl. VAT

Recycling fee 1 € included in the price

Order number: 5216028
EAN: 4251861100248

The power quality analyzer, in accordance with EN 50160, is particularly suitable for top-hat rail mounting. It is used to monitor the power quality according to common standards, e.g. EN 6100024. The UMG 605-PRO is suitable for the detection of short and long term flicker as well as for Profibus DP and Profibus DP V0. The UMG has two digital inputs and outputs and additionally a temperature measurement input.

Harmonics occur due to operating equipment with a non-linear characteristic, e.g. transformers used in saturation, energy saving bulbs, frequency converters and power electronics. They cause a load on the mains due to additional currents and can affect or even destroy operating equipment. This mains feedback can be detected and documented using power quality analysers.

The alarm management feature in GridVis® monitors all measurement parameters captured by the UMG measuring devices. It comprises escalation management, a logbook function and user management for individual notifications by e-mail, dialogue box on the monitor, etc.

In addition to monitoring effective values, short term interruptions and transients, as well as communication with the measuring devices can also be monitored.

Powerful RCM residual current monitoring already detects leakage currents in their initial stages before they cause system failures or even fires. It is already integrated in certain UMG measuring devices. The measuring current transformer that is required can be installed manually at a later date if required. Continuous RCM monitoring increases the system safety and availability significantly. In specific applications such as the data centre, residual current monitoring is essential due to the high availability requirements.

Flicker refers to the subjective impression of visibly noticeable brightness fluctuations, caused by a temporal change to the light density or the spectral distribution. The cause is voltage variations. As of a specific threshold value, flicker occurrences become disturbing and harmful to health under certain circumstances. The standard DIN EN 61000-4-15 controls the details.

Many UMG measuring devices have their own memory containing typical recording ranges of up to 2 years. Recording is freely configurable. A 128 megabyte memory can record around 5,000,000 values.

A notification by e-mail is the ideal aid for alarm and escalation management for the UMG measuring devices and the GridVis® software. Recipients can therefore be informed of the details of an event immediately.

Power quality

  • Continuous power quality monitoring (e.g. EN 50160)
  • Harmonics analysis up to the 63rd harmonic, even and odd
  • Interharmonics
  • Distortion factorTHD-U /THD-I
  • Measurement of positive, negative and zero sequence component
  • Flicker measurement in accordance with DIN EN 61000-4-15
  • Logging and storage of transients (> 50 μs)
  • Recording of short-term interruptions (> 20 ms)
  • Monitoring start-up processes
  • Recorder for limit value events

Power

  • 4 voltage and 4 current measurement inputs
  • Logging and digitalisation of effective values (true RMS) of currents and voltages (15 – 440 Hz)
  • Continuous sampling of the voltage and current measurement inputs at 20 kHz
  • Recording of over 2,000 measured values per measurement cycle (200 ms)
  • Stipulation of nominal current possible for measuring current events
  • Fourth current measurement input is suitable for measuring the current in the neutral or PE conductor or for measuring any potential difference between N and PE
  • Large measured data memory (memory range = 5 000 000 measured values)
  • Simple remote polling of measured data via the device's own homepage
  • All interfaces can be used simultaneously
  • Up to 4 ports can be accessed simultaneously
Rated voltage [V] L-N: 277 V AC, L-L: 480 V AC
Power voltage [V] 50 - 110 V AC, 50 - 155 V DC
Accuracy class 0,5S (kWh,.../5 A)
Width [mm] 107,5
Height [mm] 90
Depth [mm] 82
Weight in [g] 350
Software GridVis - Basic
Communication interface RS-232, RS-485, Profibus DP, Ethernet, Webserver / email
Protocols Modbus RTU, Modbus - Gateway, Profibus DP V0, Modbus TCP/IP, Modbus RTU over Ethernet, SNMP, BACnet (volitelný)
Memory 128 MB Flash
Overvoltage category 300 V CAT III
Distortion factor THD-U, THD-I YES
Connection (L-N, L-L) 3 / 4 - conductive
Measurement type 4-quadrant
Current measurement channels 4
Digital inputs 2
Digital / pulse output 2
Sampling frequency 50/60 Hz 20 kHz
Number of measurement records per second 20.000
Number of measuring results per second 5
Transients 50 µs
Flicker measurement YES
Clock YES
Accuracy V/A 0,2 % / 0,25 %
Integrated logic Jasic (7 Prg.)
Number of stored values ​​in memory 5.000 k
Weekly timer ANO
Uninterruptible measurement YES
Short-term event outages (recording) ANO
Measuring asymmetry YES
Residual current measurement NO
Recording of error events ANO
Consecutive / backward / null component ANO
Bi-metallic function ANO
Operating hours counter ANO
Input for temperature measurement 1
RMS value of periods (50/60 Hz) 10/12