UMG 508
We will be happy to advise you:
UMG 508
UMG 508 - 5221002 Trojfázový analyzátor sítě s jmenovitým napětím až 417/720 V AC. Napájecí napětí 44-130 V AC, 48-180 V DC. Paměť Flash, kapacita 256 MB. Rozhraní RS 485, Profibus DP, Ethernet, software GridVis.
Order number: 5221002
The UMG 508 is a three-phase network analyzer from Janitza, designed for detailed monitoring and analysis of electrical parameters in industrial and commercial applications. This device enables monitoring of power quality, detection of harmonic distortions, and optimization of energy efficiency.
Key Features:
- Power Quality Measurement: Analysis of harmonics up to the 63rd order, detection of transients, and monitoring of parameters such as voltage sags, swells, and interruptions.
- Communication Interfaces: Supports interfaces such as RS485, Profibus DP, and Ethernet, facilitating integration into existing energy management systems.
- Memory: Integrated 256 MB memory allows storage of measured data for subsequent analysis.
- Display: Color graphical display with an intuitive user interface for easy operation and visualization of measured values.
- Supply Voltage: Model 5221002 is designed for a supply voltage of 44–130 V AC or 48–180 V DC.
Technical Specifications:
| Parameter | Value |
|---|---|
| Nominal Voltage L-L | 720 V AC |
| Nominal Voltage L-N | 417 V AC |
| Supply Voltage | 44–130 V AC / 48–180 V DC |
| Current Measurement Channels | 4 |
| Digital Inputs | 8 |
| Digital Outputs | 5 |
| Memory | 256 MB |
| Sampling Frequency | 20 kHz |
| Voltage Measurement Accuracy | ±0.1 % |
| Current Measurement Accuracy | ±0.2 % |
Benefits:
- Accurate Measurement: Enables detailed analysis of electrical parameters for optimizing energy efficiency.
- Flexibility: A wide range of communication interfaces and support for various protocols facilitate integration into different systems.
- User-Friendly: Intuitive operation through the graphical display simplifies monitoring and analysis of data.
Applications:
The UMG 508 is ideal for use in industrial plants, commercial buildings, and other facilities where monitoring power quality and efficient energy management are crucial.
| Rated voltage [V] | L-L: 720 V AC, L-N: 417 V AC |
|---|---|
| Power voltage [V] | 44 - 130 V AC, 48 - 180 V DC |
| Accuracy class | 0,2S (kWh,.../5 A) |
| Width [mm] | 144 |
| Height [mm] | 144 |
| Depth [mm] | 81 |
| Weight in [g] | 1000 |
| Software | GridVis - Basic |
| Communication interface | RS-485, Profibus DP, Ethernet, Webserver / email |
| Protocols | BACnet (volitelný), SNMP, Modbus TCP/IP, Modbus RTU over Ethernet, Profibus DP V0, Modbus - Gateway, Modbus RTU |
| Memory | 256 MB Flash |
| Overvoltage category | 600 V CAT III |
| Distortion factor THD-U, THD-I | YES |
| Connection (L-N, L-L) | 3 / 4 - conductive |
| Measurement type | 4-quadrant |
| Current measurement channels | 4 |
| Digital inputs | 8 |
| Digital / pulse output | 5 |
| Sampling frequency 50/60 Hz | 20 kHz |
| Number of measurement records per second | 20.000 |
| Transients | 50 µs |
| Flicker measurement | NO |
| Clock | YES |
| Accuracy V/A | 0,1 % / 0,2 % |
| Integrated logic | Jasic (7 Prg.) |
| Number of stored values in memory | 10.000 k |
| Weekly timer | ANO |
| Uninterruptible measurement | YES |
| Short-term event outages (recording) | ANO |
| Measuring asymmetry | YES |
| Residual current measurement | NO |
| Recording of error events | ANO |
| Consecutive / backward / null component | ANO |
| Bi-metallic function | ANO |
| Operating hours counter | ANO |
| Input for temperature measurement | NE |
| RMS value of periods (50/60 Hz) | 10/12 |
Accessories