Modul FBM10R-NC

We will be happy to advise you:

Modul FBM10R-NC

Modul sběrnice Fieldbus - 1506078 Fieldbus modul s Modbus RTU Napájecí napětí 24V DC +/-20% Přenosové rychlosti: 9600, 38400 baudů Možné adresy sběrnice: 1 až 6310x PT1000 vstupy 2vodičová montáž na DIN lištu TS35V x Š x H 90 x 88 x 58mm Okolní teplo ...
Modul sběrnice Fieldbus - 1506078 Fieldbus modul s Modbus RTU Napájecí napětí 24V DC +/-20% Přenosové rychlosti: 9600, 38400 baudů Možné adresy sběrnice: 1 až 6310x PT1000 vstupy 2vodičová montáž na DIN lištu TS35V x Š x H 90 x 88 x 58mm Okolní teplota: 10°C...+50°C
show more
show less
510 € excl. VAT
617,10 € incl. VAT

Recycling fee 0,50 € included in the price

Order number: 1506078

The FBM10 series represents an inexpensive alternative to the WAGO I/O system. All FBM10 modules have an RS485 interface with the Modbus RTU protocol and can serve as slaves to the devices of the UMG 604-PRO, UMG 605-PRO, UMG 508, UMG 509-PRO, UMG 511 and UMG 512-PRO series. The devices of the UMG 104 and UMG 507 series cannot be used as masters for the FBM10 modules.

RS485 Interface

Many UMG measuring devices have an RS485 interface with Modbus RTU protocol, which enables extremely cost-effective networking. It is characterized by a simple topology structure and insensitivity to EMC interference. The communication between transmitter and receiver takes place via a shielded, twisted pair cable.

GridVis®

GridVis® is a comprehensive and scalable software for setting up an energy monitoring system and for monitoring voltage quality. It is used both for programming and configuring many UMG measuring devices and for reading out, processing and analyzing the measured data. Typical applications are power supply, industrial plants, facility management, etc.

Temperature input

The integrated temperature input for thermocouples (PT 100/1000, KTY 83 or 84) can be used in a variety of ways. In this way, sensitive system parts can be additionally protected in addition to current and voltage monitoring, e.g. transformer temperature. Typical applications are temperature monitoring in low-voltage main distribution boards, transformers or server cabinets.

Reporting

An important component of the network analysis is the report generation of GridVis®. It provides a quick and clear representation of the voltage quality in defined time periods. The power quality reports are based on international standards (EN 50160, EN 61000-2-4, IEEE 519, etc.). In addition to the PQ reports, energy consumption reports are of great benefit to the user. Generation and dispatch can take place automatically according to freely definable schedules.

Decentralized I/O Fieldbus Modules FBM10 Series

  • RS485 interface
  • Modbus RTU protocol
  • Can be used as a slave device to the measuring devices of the UMG 604-PRO, UMG 605-PRO, UMG 508, UMG 509-PRO, UMG 511 and UMG 512-PRO series
  • Connection also possible over a distance of up to 1,000 m to the RS485 Modbus master interface of the device; either via Profibus cable or e.g. a cable of the type Li2YCY(TP) 2 x 2 x 0.22
  • Modules are available ready configured and programmed according to the selected measuring device

Application of the FBM10PT1000 modules

  • Temperature field bus module
  • Recording of up to 10 temperature measurements (e.g. via PT100 or PT1000)
  • Recording and visualization of the measured values is carried out with the help of a UMG 604-PRO, UMG 605-PRO, UMG 508, UMG 509-PRO, UMG 511 or UMG 512-PRO and a required extension
  • Temperature monitoring
  • Temperature detection

Application of the FBM10I and FBM10R modules

  • Combination of different input and output signals for distribution to the corresponding participants.
  • To use the field bus modules, a connection to the respective Modbus master from the UMG 604-PRO, UMG 605-PRO, UMG 508, UMG 509-PRO, UMG 511 or UMG 512-PRO device series is required
  • All data points integrated in the Janitza system
  • Acquisition of various parameters such as process data, states, fault messages, limit values, alarm outputs, etc.
  • Archiving and visualization via GridVis® software
  • Emax blocking or enabling
  • Tariff switching
  • Emax setpoint switching
  • Synchronization measuring period
  • Fault messages
  • Status messages
  • Emax outputs
  • Limit value outputs for measured values
Power voltage [V] 250 V AC, 24 V DC
Width [mm] 88
Height [mm] 90
Depth [mm] 58
Weight in [g] 80
Software GridVis - Basic
Communication interface RS-485
Protocols Modbus RTU
Relay output 10
Digital inputs YES

Accessories

No item