Power Quality Monitoring Device UMG 510
Applications
The power quality analyser which is equipped with 4 current and voltage inputs collects and digitalises the effective values (True RMS) from currents and voltages in 50-70Hz networks. The integrated microprocessor calculates the electrical parameters from the sampling values. The relevant voltage can be defined as a phase-neutral or a phase-phase voltage for measurement in a three-phase system. The voltage serves the UMG 510 as a reference voltage for harmonic measurement, transient and event recording and for the flicker meter. A nominal current can be set using this for the measurement of electrical current events.
The 4th current and voltage input represents a separate measurement system. However, it is generally used for measuring the current in the neutral or PE conductor or used for measuring a voltage difference between N and PE.
Areas of application
- Checks on the feeders in accordance with EN50160
- Checks on the internal distribution network according to EN61000-2-4
- Analysis of electrical faults for network problems
- Continuous monitoring of the power quality
Display examples
The graphic, illuminated display on the UMG 510 enables the presentation of measurement values in numerical form, as a bar chart or as a line graph.
Selected displays can automatically be displayed in alternation (automatic display rotation). The instrument is programmed using clear text menus or the PAS510 software.