“Deeper” measurements (sub-distributions or end consumer/individual output) are measured more and more conmow in electrical installations. The nominal current are, therefore, relatively low (63, 35 or 16A), the space is restricted and the accuracy of the current transformer must be sufficient for the power measurement (minimum class 1). These characteristics are often difficult to combine.

The DINCT64/1/1 combines these characteristics in a single product. Due to the unique construction, no solder, crimp or clamp connections are required. The secondary leads are 1 meter long.

Dimensional drawing

 

Technical data

 
Transmission ratio: 64/1A (32/1A & 16/1A)
Accuracy: Class 1
Power: 0,5VA
Icth; cont. limit current: 120%
Ith; thermal limit current 60xIn/1s
Frequency: 50Hz
Secondary lead diameter: 0,5mm²
Ambient temperature: 45°C max.
Standard: IEC6000-44-1
Material: PA6.6
Item number: 15.02.849