Universal measuring device UMG 96

Measurement parameter Display range Measurement range
at scalierung factor 1
L1 L2 L3 Sum Lowest value Average
value*1
Max value Measurement
accuracy
Average Measurement
Current.. 1/5A L1-L3 0,00 .. 9,99 kA 0,02 .. 5 A dot dot dot dot   dot dot dot +-1 % rng
Current, calculated in N 0,00 .. 9,99 kA 0,03 .. 15 A dot dot dot   dot dot dot dot +-3 % rng
Voltage L-N 0,0 .. 34 kV 196 .. 275 V AC *2 dot dot dot   dot     dot +-1 % rng
Voltage L-L 0,0 .. 60 kV 340 .. 476 V AC *2 dot dot dot         dot +-2% rng
Frequency (U) 45 .. 65 Hz 45 .. 65 Hz dot               +-1,5 % rdg
Effective power, +/- 0,00 W .. 99,9 MW 3,2 W .. 1,375 kW dot dot dot dot   dot dot*4 dot +-1,5 % rng
Apparent power 0,00 VA .. 99,9 MVA 3,2 VA .. 1,375 kVA dot dot dot dot   dot   dot +-1,5 % rng
Reactive power 0,00 var .. 99,9 mvar 3,2 var .. 1,375 kvar dot dot dot dot   dot     ind.+-1,5 % rng
cos phi 0,00 ind. ..1,00 .. 0,00 kap.. 3,2 kap. .. 1,00 .. 0,00 ind.. dot dot dot dot         +-3 % rng*4
Effective energy, consumed 0 .. 999.999.999 kWh         dot         *3
Reactive energy, inductive 0 .. 999.999.999 kvarh         dot          
Operating hour 0 .. 999.999.999 h                   +-2 min per day

rng: of measurement range, rdg: of measurement value
*1 integration over time: 5, 15, 30, 60, 300, 480, 600 and 900 seconds
*2 also available: measurement range: L-N 49 .. 76V / L-L 85 .. 132V and L-N 98 .. 140V / L-L 170 .. 242V
*3 accuracy class 2 according to EN61036:1996, VDE0418 part 7:May 1997, IEC1036:1996
*4 Only for sum values, *5 The measured apparent power must be in a range between 1 and 100%.