Power analyser UMG 104

Features
Memory Measurement data 4 MB
Clock   +/- 1 min per month
Operating hours counter   Yes
Tarifs   4 x real energy / 4 x reactive energy
Peripherals
Digital inputs as status or pulse input 2
Digital outputs as switching or pulse output 2
Temperature input PT100, PT1000, KTY83, KTY84 1
Password protection   Yes
Software GridVis Yes
Communication Interfaces
RS 232 9.6, 19.2, 38.4, 115.2 kbps Yes
RS 485 9.6, 19.2, 38.4, 76.8, 115.2, 921.6 kbps Yes
Profibus DP Sub D9-pole up to 12 Mbps Yes, Variant P
Communication Protocols
Modbus RTU   Yes
Profibus DP V0   Yes, Variant P
Technical data
Voltage measurement 3-phase 4-wire grid (L-N, L-L)
3-phase 3-wire grid (L-L)
277/480 V AC
480 V AC
Overvoltage class   300 V CATIII
Quadrants   4
Continuous Measurement   Yes
Sampling rate, 8 channels per channel 20 kHz
Weight   350 g
Dimensions   L=107,5 mm x B=90 mm x H=82 mm
Mounting according to IEC EN60999-1/ DIN EN 50022 35 mm DIN rail
Working temperature   -10…55 °C
Connectable wires (U/I) one wire, more wires, fine stranded wires
cable end sleeve
0.08 - 2.5 mm²
1.5 mm²
Protection class according to EN60529 IP 20
Measuring range
Voltage L-N, AC (without PT)   10…300 V AC
Voltage L-L, AC (without PT)   17…520 V AC
Current (Transformer:: x/1 und x/5 A)   0.005..7,5 A
Frequency of fundamental   45 ..65 Hz
Grids   IT, TN, TT
Measurement in grids   1 ph, 2 ph, 3 ph, 4 ph and up to 4 times 1ph
Measured values
Voltage L1, L2, L3, L4, L1-L2, L2-L3, L1-L3 accuracy ±0.2 %
Current L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 accuracy ±0.2 %
K-factor L1, L2, L3, L4 Yes
Rotating current components Positive/ Negative/ Zero Phase Sequence Yes
Real, apparent, reactive power L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 accuracy ±0,4 %(EN61557-12)
Cos-phi / power factor L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 Yes
Phase angle L1, L2, L3, L4 Yes
Real energy (kWh) L1, L2, L3, L4, Sum L1-L3, Sum L1-L4:
- Consumed real energy (rate 1, rate 2)
- Supplied real energy (rate 1, rate 2)
Class 0.5S (…/5 A),
Class 1 (…/1 A)
Reactive energy (Karh) L1, L2, L3, L4, Sum L1-L3, Sum L1-L4:
- Inductive energy (rate 1, rate 2)
- Capacitive reactive energy
Class 2
Reactive energy (kVAh) L1, L2, L3, L4, Sum L1-L3, Sum L1-L4 Yes
Wave form voltage L1, L2, L3, L4 Yes
Frequency of mains   accuracy ±0.01 Hz
Temperaturmessung   accuracy ±1.5% rng
Average values   Yes
Minimum and maximum values   Yes
Power quality
Harmonics, 1st- 40th Current, voltage, real/reactive power (±)
L1, L2, L3, L4
accuracy V, I Class 1 (EN61000-4-7)
Distortion factor THD-U in % L1, L2, L3, L4 Yes
Distortion factor THD-I in % L1, L2, L3, L4 Yes
Unbalance   Yes
Positive/ Negative/ Zero Phase Sequence   Yes
Inrush-currents 10 ms No
Malfunction writer   No
Short-term interruptions   No