Electronic pulse output – energy meter, H series

Type WH6165 DVH3113 MDVH3106
Item number 14.01.020 14.01.021 14.01.022
Accuracy class 1 2 (1 optional) 1
Protection class 2 2 2
Direct measurement Basis / Limit 10 / 65A 5 / 65A -
Current transformer - - ../5A*1
Power consumption in current path - - <1,0VA
Current inputs sep. galvanically - - Yes
Minimum working current 40mA 25mA 25mA
Measuring voltage 230V+/-10% 3x230/400V +-10% 3x230/400V +-10%
Self consumption <1,5VA <1,5VA <1,5VA
Frequency 50/60Hz 50/60Hz 50/60Hz
Pulse output SO value 1000 pulses/kWh 500 pulses/kWh 5000 pulses/kWh
Pulse width min. 30ms min. 30ms min. 30ms
Load   up to 230V AC /100mA  
Number of digits 6,1 6,1 5,2
PTB accreditation Yes Yes Yes
Calibratable optional optional optional
Protection housing/terminals   IP51/IP20  

Connection diameter

up to 16qmm up to 25qmm current:10qmm
voltage: 2,5qmm
Width 36mm 2TE 125mm 7TE 125mm 7TE
Dimensions B36xH96xT66mm B125xH96xT66mm B125xH96xT66mm
Weight 140g 500g 500g
Operating temperature -20 .. +55°C -20 .. +55°C -20 .. +55°C
Storage temperature -25 .. +70°C -25 .. +70°C -25 .. +70°C